Concrete Shear Strength

...

The proper selection of the governing provision in LRFD can summarized by the following flow chart:

4-sided structure

Fill depth >= 2 feet

Use 5.14.5.3 for slabs

Use 5.8.3/5.7.3 for walls

If wall thickness >= 16” or member is in tension, use 5.8.3.4.2/5.7.3.4.2 (beta calculated using App. B5)

If wall thickness < 16”, use 5.8.3.4.1/5.7.3.4.1 (beta is a constant 2.0)

Fill depth < 2 feet

Use 5.8.3/5.7.3 for all members

If member thickness >= 16”  or member is in tension, use 5.8.3.4.2/5.7.3.4.2 (beta calculated using App. B5)

If member thickness < 16”, use 5.8.3.4.1/5.7.3.4.1 (beta is a constant 2.0)

3-sided structure

Any fill depth

Use 5.8.3/5.7.3 for all members

If member thickness >= 16”  or member is in tension, use 5.8.3.4.2/5.7.3.4.2 (beta calculated using App. B5)

If member thickness < 16”, use 5.8.3.4.1/5.7.3.4.1 (beta is a constant 2.0)

Note that the iterative beta method (beta calculated using Appendix B) is actually usable in all situations, regardless of the member thickness or location.

...